http://www.thisishullandeastriding.co.uk/news/Undefined-Headline/article-3373086-detail/article.html
or http://tinyurl.com/68kao8g
Probably written by someone with a proverbial lack of knowledge, but
this bit puzzled me:
'All properties in the UK have electricity supplied at 240 volts.
However, without copper earthing, this can soar to 400 volts'.
Any ideas?
> 'All properties in the UK have electricity supplied at 240 volts.
> However, without copper earthing, this can soar to 400 volts'.
415v between phases, 240 phase to neutral. The neutral is bonded to
real earth at the substation. Remove that bond and weird things can
happen depending on how well balanced the load is on the 3 phases. It
may also be influenced by how the loads are connected, delta or star.
That is about the extent of my 3 phase knowledge, someone will be
along in a while with chapter and verse.
--
Cheers
Dave.
> 415v between phases, 240 phase to neutral. The neutral is bonded to
> real earth at the substation. Remove that bond and weird things can
> happen [...]
It's neutral, not earthing, links that are being stolen, AFAIK. Each
outgoing circuit will have three line fuses and a solid neutral link,
the last being removable for complete isolation. Take away the neutral
bond on an unbalanced 3-ph 4-wire circuit and you unbalance the phase
voltages, some rising and some falling, wrt the now-floating neutral
conductor in the cable.
--
Andy
In Norway there is no Neutral. Everyone gets three phases and the
sockets in each room uses two of them. there is 220V between the
phases. there's a fuse in each of the three.
I was told the reason was to reduce the maximum voltage relative to
earth.
if you blow one fuse then you end up having some rooms with their
sockets in series with the sockets in another room - turn on the
heater in one room and the TV comes on in the next room etc.
Robert
All supplies are 415v 3 phase, which is 415v measured from any phase to
any other phase. The 240v is derived by connecting from any one of
those phases to a Neutral wire which is effectively the ground/ earth
connection at the sub-station. Basically, the idea is that all of the
240v supplies should be equally balanced loads on each phase, so that
no current flows down the neutral. Now if someone removes that bit of
bus-bar which connects it to ground and should the 240v supplies happen
to be badly balanced, then that 240v can rise upto the phase to phase
voltage of 415v. So instead of the 240v a domestic consumer might get
normally, they get 415v instead.
--
Regards,
Harry (M1BYT) (L)
http://www.ukradioamateur.co.uk
> All supplies are 415v 3 phase, which is 415v measured from any phase
> to any other phase. The 240v is derived by connecting from any one of
> those phases to a Neutral wire which is effectively the ground/ earth
> connection at the sub-station. Basically, the idea is that all of the
> 240v supplies should be equally balanced loads on each phase, so that
> no current flows down the neutral. Now if someone removes that bit of
> bus-bar which connects it to ground and should the 240v supplies
> happen to be badly balanced, then that 240v can rise upto the phase
> to phase voltage of 415v. So instead of the 240v a domestic consumer
> might get normally, they get 415v instead.
Is there a reasonable chance that something would burn out and (hopefully)
trip the mains switch?
--
Murphy's ultimate law is that if something that could go wrong doesn't,
it turns out that it would have been better if it had gone wrong.
It happened to a housing development I was in 25 years ago. Builders
dug through the UG cable neutral and left 400 v on some flats due to
unbalanced load. Midlands Electric, as it was then, replaced a large
number of TV's, kettles,fridges, heaters etc. etc. which went up in
smoke and flames. No one injured fortunately.
rusty.
>Harry Bloomfield wrote:
>
>> All supplies are 415v 3 phase, which is 415v measured from any phase
>> to any other phase. The 240v is derived by connecting from any one of
>> those phases to a Neutral wire which is effectively the ground/ earth
>> connection at the sub-station. Basically, the idea is that all of the
>> 240v supplies should be equally balanced loads on each phase, so that
>> no current flows down the neutral. Now if someone removes that bit of
>> bus-bar which connects it to ground and should the 240v supplies
>> happen to be badly balanced, then that 240v can rise upto the phase
>> to phase voltage of 415v. So instead of the 240v a domestic consumer
>> might get normally, they get 415v instead.
>
>Is there a reasonable chance that something would burn out and (hopefully)
>trip the mains switch?
We had a copier burn out at work one night, due to some
ill-executed site electrical maintenance. Luckily the smoke was
spotted before it took the building with it.
Chris
--
Chris J Dixon Nottingham UK
ch...@cdixon.me.uk
Have dancing shoes, will ceilidh.
I've noticed that the copper lightning earth's at communication sites
are now being replaced with Ally and signs to the effect of "No Copper
on this site" are starting to appear..
--
Tony Sayer
Taking the Sky box first - so not all bad.
--
Skipweasel - never knowingly understood.
Alpha mark to Adam.
(He would have merited 'Alpha +' for "pikeys, and our best hope is a
genetic engineering solution")
--
Robin
PM may be sent to rbw0{at}hotmail{dot}com
> In Norway there is no Neutral. Everyone gets three phases and the
> sockets in each room uses two of them. there is 220V between the
> phases. there's a fuse in each of the three.
That's 3-ph 3-wire rather than the more usual 3-ph 4-wire. The downside
is the low line voltage 230 V rather than 400, so currents are higher.
Do industrial & commercial premises get the same, or a higher voltage?
> I was told the reason was to reduce the maximum voltage relative to
> earth.
Isn't it an IT system too? How are earth faults detected and cleared?
> if you blow one fuse then you end up having some rooms with their
> sockets in series with the sockets in another room - turn on the
> heater in one room and the TV comes on in the next room etc.
Linked 3-pole MCBs would prevent that.
--
Andy
> I've noticed that the copper lightning earth's at communication sites
> are now being replaced with Ally and signs to the effect of "No Copper
> on this site" are starting to appear..
Sounds like a different sort of copper is called for...
--
Andy
"Part timer" <hhmn...@gmail.com> wrote in message
news:b1b93777-eeb5-4623...@y26g2000yqd.googlegroups.com...
> Any ideas?
Do what I did a few weeks ago, phone 999 and have the idiot arrested.
Call the network operator too as the police won't enter the substation.
I have identified the problem. YOU suggested the solution, is it your own
idea?
--
Adam
You got yourself arrested?
--
Adam
And it was a first class solution.
> YOU suggested the solution, is it your
> own idea?
Ummm - I'm not sure - I think that Austrian bloke who was painter in the
1910s might have had it first. But I don't want to be a DIY China
syndrome so I hope it's OK if I (i) stop digging and (ii) go to the pub.
Bugger - I meant of course a first class identification of the problem.
(Why didn't SWMBO look over my shoulder sooner? Why doesn't the toast
know to land butter side up? Why doesn't Pi = 3? .........)
You could blame the Jews:-)
--
Adam
What? Gene pool cleansing through early-life electrocution? ;)
> Why doesn't the toast know to land butter side up?
'cos the butter moves the centre of mass slightly butter-side-wards,
so
a randomly spinning buttered slice is more predispensed to land on the
side nearest the centre of gravity - the buttered side.
Ypou could balance it out by buttering both sides, then it's equally
likely to land on either side...
JGH
> Probably written by someone with a proverbial lack of knowledge, but
> this bit puzzled me:
Yes, it's a real problem. Pikeys are now smart enough to realise that
nicking live busbars tends to end in Flaming Sparky Death, so they're
focussing on the earth straps instead. Once no longer bonded, it's
easy for domestic supplies to start floating around by a few hundred
volts.
> I've noticed that the copper lightning earth's at communication sites
> are now being replaced with Ally and signs to the effect of "No Copper
> on this site" are starting to appear..
MODplod overtime is supposed to have gone up recently too, patrolling
the perimeters of aerial farms.
Yes they nicked a lightning earth from a comms site near Peterborough
around 6 inches of copper braiding, makes me wonder just how much it
cost them in petrol to drive there and take it !?..
--
Tony Sayer
Come on Tony, do you actually think they paid for the petrol??
They also pinched the copper earth strapping from Kempston MF a few
years ago, the quick fix was rather inventive.
http://tx.mb21.co.uk/gallery/bedford_kempston-bp-01.jpg
http://tx.mb21.co.uk/gallery/bedford_kempston-bp-02.jpg
--
Bill
[snip]
> Yes they nicked a lightning earth from a comms site near Peterborough
> around 6 inches of copper braiding, makes me wonder just how much it
> cost them in petrol to drive there and take it !?..
Stolen Red Diesel ;-)
--
Jim White Wimbledon London England
I will not torment the emotionally frail
Well I suppose we can take that as read;!..
>
>They also pinched the copper earth strapping from Kempston MF a few
>years ago, the quick fix was rather inventive.
>
>http://tx.mb21.co.uk/gallery/bedford_kempston-bp-01.jpg
>
>http://tx.mb21.co.uk/gallery/bedford_kempston-bp-02.jpg
The earths for the new re-built Peterborough mast were nicked even
before they started transmissions;!..
>
>
--
Tony Sayer
MoD plod? That sort of job is usually done by GuardFarce.