ABCDEFGHIJKLMNOPQRSTUVWXYZAAABACADAE
1
2
OILNATURAL GAS
3
Date4/21/119/27/128/21/1311/23/13Date
4
System Changen/aInstall 250 MBH HeadBaselineAdd BafflesBaffles + Restrict Comb. AirSystem Change
5
Control Voltagevdcn/an/a2.05.05.55.52.02.02.03.04.05.0Control Voltage
6
Firing RateMBH24524558240262262787878153212248MBHFiring Rate
7
Stack TempdegF554492422760785690600575580627660686degFStack Temp
8
Primary TempdegF6678.480807575757575757575degFPrimary Temp
9
Net TempdegF488413.6342680710615525500505552585611degFNet Temp
10
Comb Air Restriction%n/an/a000005065505050%Comb Air Restriction
11
O2%6.77.1106.25.86.24.42.44.64.84.8%O2
12
CO2%10.610.26.18.2%CO2
13
COppm6114011162350368ppmCO
14
NOppm----615ppmNO
15
NO2ppm----12ppmNO2
16
NOxppm----818ppmNOx
17
Excess Air%43.751.491423437.523.711.525.127.226.5%Excess Air
18
Efficiency%80.681.878.371.977.079.180.381.179.578.578%Efficiency